受潮复合缺陷对直埋110kV电缆中间接头电热特性的影响
DOI:
作者:
作者单位:

1.山东理工大学电气与电子工程学院;2.山东七星电气科技发展有限公司

作者简介:

通讯作者:

中图分类号:

TK124

基金项目:

国家自然科学(52477147);


Effects of Moisture-Related Composite Defects on the Electrothermal Characteristics of Directly Buried 110 kV Cable Intermediate Joints
Author:
Affiliation:

1.School of Electrical and Electronic Engineering,Shandong University of Technology;2.Shandong Qixing Electric Technology Development Co,Ltd

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    直埋硅橡胶预制式电缆中间接头容易受潮并引发绝缘故障,为揭示其在受潮缺陷下的热风险响应特性,本文分析典型缺陷区域的局部电热特征。采用COMSOL Multiphysics软件建立三维电缆中间接头电.磁.热耦合有限元模型,分别引入导电、半导电、绝缘三种球体颗粒缺陷,并设置η表示不同厚度水膜覆盖球体缺陷程度,即部分覆盖、恰好覆盖、完全覆盖三种不同工况,分析不同受潮状态下的电缆中间接头缺陷部位的电场与温度分布规律,并以实际典型故障验证仿真分析结果。研究结果表明,缺陷区域易形成局部电场畸变和焦耳热集中,导致明显的热点效应。导电性缺陷在η≤1工况时显著影响缺陷区域的电场畸变和局部温升;绝缘性缺陷在η>1工况时对电热场扰动最为剧烈。导电球体杂质且在η=1工况下,最易造成电场畸变和局部温升,是热失控风险最高的场景,需在工程设计中重点规避。本研究揭示电缆中间接头的绝缘受潮失效机理,可为其结构优化、防潮密封设计及受潮故障诊断提供理论依据。

    Abstract:

    The intermediate joints of directly buried silicone rubber prefabricated cables are prone to moisture and cause insulation faults. In order to reveal the thermal risk response characteristics under moisture defects, this paper analyzes the local electrothermal characteristics of typical defect areas. COMSOL Multiphysics software was used to establish a three-dimensional cable intermediate joint electricity. Magnetic. In the thermal coupling finite element model, three kinds of spherical particle defects, conductive, semi-conductive and insulating, are introduced respectively, and η is set to represent the degree of spherical particle defects covered by water films of different thicknesses, namely, partial coverage, proper coverage and complete coverage. The electric field and temperature distribution of the defect parts of the cable intermediate joint under different moisture conditions are analyzed, and the simulation results are verified by actual typical faults. The results show that the defect region is easy to form local electric field distortion and Joule heat concentration, resulting in obvious hot spot effect. The conductive defects significantly affect the electric field distortion and local temperature rise in the defect area when η ≤ 1. The insulation defect has the most severe disturbance to the electrothermal field when η > 1. The conductive sphere impurity is most likely to cause electric field distortion and local temperature rise under the condition of η = 1, which is the scene with the highest risk of thermal runaway and needs to be avoided in engineering design. This study reveals the failure mechanism of insulation moisture of cable intermediate joints, which can provide theoretical basis for its structural optimization, moisture-proof seal design and moisture fault diagnosis.

    参考文献
    相似文献
    引证文献
引用本文

李斌慧,咸日常,孙晓维,等. 受潮复合缺陷对直埋110kV电缆中间接头电热特性的影响[J]. 科学技术与工程, , ():

复制
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2026-02-12
  • 最后修改日期:2026-04-09
  • 录用日期:2026-05-10
  • 在线发布日期:
  • 出版日期:
×
2026年会通知 | “技术经济学驱动智能经济生态构建与治理变革”——中国技术经济学会第三十三届学术年会(2026)会议通知暨征文启事(第一轮)
亟待确认版面费归属稿件,敬请作者关注